HANGZHOU ZION COMMUNICATION CO., LTD

Our Purpose To provide better signal transmission products and solutions in the world. Our Mission Focusing on customer needs, we provide customers with more competitive signal transmission products,

Manufacturer from China
Verified Supplier
10 Years
Home / Products / Low Voltage Power Cables /

H05VV-F Flexible Cable

Contact Now
HANGZHOU ZION COMMUNICATION CO., LTD
Visit Website
City:hangzhou
Province/State:zhejiang
Country/Region:china
Contact Person:MrJames
Contact Now

H05VV-F Flexible Cable

Ask Latest Price
Video Channel
Brand Name :Zion communication OR OEM
Model Number :H05VV-F Flexible Cable
Certification :CE, RoHS, VDE, UL, CUL, LPCB
Place of Origin :China
MOQ :20 KM
Payment Terms :T/T, L/C
Supply Ability :1000KM / Month
Delivery Time :25 working days
Packaging Details :100M, 200M, Roll, Carton
Conductor :Class 5 flexible copper
Insulation :Polyvinyl Chloride (PVC)
Sheath :Polyvinyl Chloride (PVC)
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description
H05VV-F Flexible Cable

H05VV-F Flexible Cable

H05VV-F Flexible Cable

Application: Cable Standards:
Ordinary duty PVC cable for use in
domestic appliances,kitchens and offices.
For use with light portable appliances
such as table lamps and office equipment.
Generally unsuitablefor outdoor use or
industrial applications.
EN 50525-2-11, EN 60228
Flame Retardant according to IEC/EN 60332-1-2
Product Description:
Conductor Class 5 flexible copper
Insulation Polyvinyl Chloride (PVC)
Sheath Polyvinyl Chloride (PVC)
Characteristics:
Voltage Rating Uo/U H05V-K: 300/500V
Temperature Rating +5°C to +70°C
Minimum Bending Radius Fixed: 8 x overall diameter
Core Identification:
2 Core: Blue Brown
3 Core: Blue Brown Green/Yellow
4 Core: Brown Black Grey Green/Yellow
5 Core: Brown Black Grey Blue Green/Yellow
*E3184Y Core Identification:
4 Core: Brown Black Grey Green/Yellow
* Should not be installed at temperatures below 0°C
Dimensions:
Zion Code No. Of
Cores
Nominal Cross Sectional Area(mm²) Nominal Thickness Of Insulation
(mm)
Nominal Overall
Diameter
(mm)
Nominal Weight
(mm)
H05VV-F2x0.75 2 0.75 0.6 6.3 57
H05VV-F2x1 2 1.00 0.6 6.6 65
H05VV-F2x1.5 2 1.50 0.7 7.4 84
H05VV-F2x2.5 2 2.50 0.8 9.1 130
H05VV-F3x0.75 3 0.75 0.6 6.7 68
H05VV-F3x1 3 1.00 0.6 7.0 78
H05VV-F3x1.5 3 1.50 0.7 8.1 108
H05VV-F3x2.5 3 2.50 0.8 9.9 163
H05VV-F3x4 3 4.00 0.8 11.3 227
H05VV-F4x0.75 4 0.75 0.6 7.3 82
H05VV-F4x1 4 1.00 0.6 7.9 100
H05VV-F4x1.5 4 1.50 0.7 9.0 134
H05VV-F4x2.5 4 2.50 0.8 10.8 201
H05VV-F5x0.75 5 0.75 0.6 8.1 102
H05VV-F5x1 5 1.00 0.6 8.6 120
H05VV-F5x1.5 5 1.50 0.7 10.0 166
Conductors:
Nominal Cross Sectional Area(mm²) Maximum Diameter
Of Wires In Conductor
MAXIMUM RESISTANCE OF CONDUCTOR AT 60ºC
ohms/km
Plain Wires
0.75 0.21 26.00
1 0.21 19.50
1.5 0.26 13.30
2.5 0.26 7.98
4 0.31 4.95
The above table is in accordance with EN 60228
Class 5 Flexible Copper Conductors for Single Core and Multi-Core Cables
Current Carrying Capacity
Nominal Cross Sectional Area (mm²) Current Carrying Capacity Amps Maximum Mass Supportable
By Twin Flexible Cord
Kg
Single-Phase AC Three-Phase AC
0.75 6.0 6.0 3
1 10.0 10.0 5
1.5 16.0 16.0 5
2.5 25.0 25.0 5
4 32.0 32.0 5
The above table is in accordance with Table 4F3A of the 17th Edition of IEE Wiring Regulations.
Voltage Drop:
Nominal Cross Sectional Area (mm²) DC Or Single-phase AC
(mV/A/m)
Three-phase AC
(mV/A/m)
0.75 62.0 54.0
1 46.0 40.0
1.5 32.0 27.0
2.5 19.0 16.0
4 12.0 10.0
Conductor operating temperature: 60ºC
The above table is in accordance with Table 4F3B of the 18th Edition of IEE Wiring Regulations BS7671 and IEC 60364-5-52.
Inquiry Cart 0