Our Purpose To provide better signal transmission products and solutions in the world. Our Mission Focusing on customer needs, we provide customers with more competitive signal transmission products,
The cable is designed for installation under plaster, in flat, concealed installation and for installation in conduits and cable ducts. The cable is resistant to flame propagation according to the requirements of fire technical characteristics given acc. to Decree No.246/2001 Col. At these cables you can easily recognize 2 main types: 3 × 1,5 mm2 always with blue stripe and 3 × 2,5 mm2 always with green stripe. Installation of the product should only be carried out by personnel trained and qualified for electrical works. The product is designed according to recognized standards. Applicable rules of installation must be applied at all times.
Zion's Hot Types
Properties:
Rated voltage
450/750 V
Colour of sheath
Black with blue or green stripe
Test voltage
2,5 kV
Flame spread resistance
IEC 60332-1; VDE 0482 T332-1-2
Maximal short-circuit temperature
+160 °C
CPR class
ECa
Maximal conductor operating temperature
+70 °C
UV stability
Yes
Temperature range for handling
From −30 up to +70 °C
Packaging
Coils and drums
Minimal temperature for laying and manipulation
+5 °C
Certificate
Minimal storage temperature
−30 °C
RoHS
Yes
Colour of insulation
HD 308 S2
REACH
Yes
Mechanical properties:
No. of cores and cross-section
Shape of conductor
Nominal insulation thickness
Nominal sheath thickness
Diameter approx.
Cable mass approx.
Bending radius
mm2
mm
mm
mm
Kg/km
mm
3x1,5
RE
0,7
0,4
4,1x10,5
68.00
25.0
3x2,5
RE
0,8
0,4
4,8x12,6
104.00
29.0
Electrical properties:
No. of cores and cross-section
Shape of conductor
DC resistance at 20 °C (min.)
Current carrying cap. in air *)
Current carrying cap. in ground
mm2
Ω/km
A
A
3x1,5
RE
12,531
18,5
28.00
3x2,5
RE
7,519
25.00
36.00